Columns – lintels calculation table

Vertical and horizontal distance for various sizes of “Superblock” According to BS 5628 Part 1 : 1992 standard For side load equals to 25 kg/m2
( Interior Wall )

Simply Supported on 4 edges

Table 1

Wall height or the distance between lintels
(H meter)

Wall length without columns
or the distance between columns
(L meter )

 

Superblock thickness (cm)

 

7

7.5

8

9

10

12

2.0

4.9

5.6

6.4

7.8

8

8

2.3

4.3

5

5.7

7.2

8

8

2.5

3.6

4.2

4.9

6.5

8

8

2.8

3.2

3.8

4.3

5.8

7.3

8

3.0

2.9

3.4

3.9

5.1

6.7

8

3.3

 

3.1

3.5

4.5

6.2

8

3.5

 

3

3.3

4.2

5.4

8

3.8

 

 

3.2

3.9

4.8

7.6

4.0

 

 

3.1

3.7

4.6

7.0

4.3

 

 

 

3.6

4.3

6.3

4.5

 

 

 

3.5

4.1

5.7

4.8

 

 

 

3.4

4

5.6

5.0

 

 

 

3.2

3.9

5.3

5.3

 

 

 

 

3.8

5.0

5.5

 

 

 

 

3.6

4.8

5.8

 

 

 

 

 

4.7

6.0

 

 

 

 

 

4.6


Vertical and horizontal distance for various sizes of “Superblock” According to BS 5628 Part 1 : 1992 standard for side load equals to 25 kg/m2
( Interior Wall )

Simply Supported on 4 edges

Table 2

Wall height
or the distance between lintels
(H meter )

Wall length without columns
or the distance between columns
(L meter )

 

Superblock thickness (cm)

 

7

7.5

8

9

10

12

2.0

3.3

3.8

4.3

5.4

6

6

2.3

2.94

3.3

3.8

4.8

6

6

2.5

2.64

3

3.4

4.3

5.4

6

2.8

2.4

2.76

3.1

3.9

4.9

6

3.0

2.2

2.5

2.8

3.6

4.5

6

3.3

 

2.6

3.3

4.1

5.9

3.5

 

 

2.4

3.1

3.8

5.5

3.8

 

 

 

2.9

3.6

5.1

4.0

 

 

 

2.7

3.3

4.8

4.3

 

 

 

 

3.1

4.5

4.5

 

 

 

 

3

4.3

4.8

 

 

 

 

2.8

4

5.0

 

 

 

 

2.7

3.8

5.3

 

 

 

 

 

3.7

5.5

 

 

 

 

 

3.5

5.8

 

 

 

 

 

3.3

6.0

 

 

 

 

 

3.2


For various sizes of “Superblock” According to Bangkok standard For side load equals to 50 kg/m2
(Exterior Wall)
not higher than 10 m.

 

Simply Supported on 4 edges

Table 3

Wall height or the distance between lintels
(H meter )

Wall length without columns or the
distance between columns
(L meter )

 
Superblock thickness (cm)

 

7

7.5

8

9

10

12

1.350

4.30

4.50

4.90

5.50

6.20

7.40

1.500

3.20

4.00

4.75

5.50

6.20

7.40

1.750

2.50

3.00

3.50

4.00

6.20

7.40

2.000

2.20

2.50

2.75

3.90

5.90

7.40

2.250

2.00

2.25

2.60

3.35

4.30

7.40

2.500

1.90

2.15

2.35

2.95

3.65

6.00

2.750

1.85

2.00

2.25

2.70

3.25

4.95

3.000

1.75

1.95

2.15

2.55

3.00

4.45

3.250

 

1.90

2.05

2.45

2.85

4.00

3.500

 

1.85

2.00

2.35

2.75

3.75

3.750

 

 

2.00

2.30

2.65

3.50

4.000

 

 

2.00

2.25

2.60

3.45

4.250

 

 

 

2.25

2.55

3.35

4.500

 

 

 

2.25

2.50

3.25

4.750

 

 

 

2.25

2.50

3.15

5.000

 

 

 

2.25

2.50

3.10

5.250

 

 

 

 

2.50

3.05

5.500

 

 

 

 

2.50

3.00



For various sizes of “Superblock”
According to Bangkok standard
For side load equals to 80 kg/m2
(Exterior Wall)
higher than 10 m.
but not exceed 20 m.
Simply Supported on 4 edges

Table 4

Wall height or the distance between lintels
(H meter )

Wall length without columns or the
distance between columns (L meter )

 
Superblock thickness (cm)

 

7

7.5

8

9

10

12

1.35

2.05

2.50

3.00

4.25

4.90

5.85

1.50

1.80

2.00

2.25

3.35

4.90

5.85

1.75

1.50

1.80

2.00

2.65

3.45

5.85

2.00

1.50

1.65

1.85

2.30

2.75

4.50

2.25

1.40

1.50

1.75

2.00

2.50

3.50

2.50

1.40

1.50

1.60

1.95

2.30

3.25

2.75

1.40

1.50

1.60

1.90

2.20

3.00

3.00

1.40

1.50

1.60

1.80

2.00

2.80

3.25

 

1.50

1.60

1.80

2.00

2.60

3.50

 

1.50

1.60

1.80

2.00

2.60

3.75

 

 

1.60

1.80

2.00

2.40

4.00

 

 

1.60

1.80

2.00

2.40

4.25

 

 

 

1.80

2.00

2.40

4.50

 

 

 

1.80

2.00

2.40

4.75

 

 

 

1.80

2.00

2.40

5.00

 

 

 

1.80

2.00

2.40

5.25

 

 

 

 

2.00

2.40

5.50

 

 

 

 

2.00

2.40